Conduit Fill Calculator

Calculate minimum conduit trade sizes instantly based on NEC Chapter 9 Tables 4 & 5. Designed for THHN/THWN-2 standard conductors.

Calculator Inputs

4 Wires
1102030

Note: Include equipment grounding conductors in your total wire count per NEC fill rules.

Real-Time Results

Recommended Conduit Size

Calculation ReadyBased on your inputs, here is the minimum required trade size.

2" EMT

Total Conductor Area:1.0716 sq in
Actual Fill Percentage:31.9%
NEC Allowed Fill (4 Wires):40% max
Disclaimer: Sizing is based on standard NEC Chapter 9 Tables. Actual internal dimensions may vary slightly by manufacturer. Always verify local code amendments and exact conduit specs prior to installation.

Email this calculation to yourself

Keep a record of your 2" EMT sizing for your current estimate.

Looking to automate your full estimating process?

Explore the MoonLead Estimator

Frequently Asked Questions

What is the maximum allowable conduit fill?

According to NEC Chapter 9, Table 1, the allowable fill is 53% for 1 conductor, 31% for 2 conductors, and 40% for over 2 conductors.

Do equipment grounding conductors count toward conduit fill?

Yes, all conductors including equipment grounding conductors, bare or insulated, must be counted when calculating conduit fill according to the NEC.